TO RELOAD SYSTEM
|
||
|
||
AFTER PM GO TO SHEET 1
|
||
|
||
AFTER HARD/SOFT CRASH GO TO SHEET 5
|
||
|
||
AFTER POWER FAILURE GO TO SHEET 6
|
||
|
||
IF NONE OF ABOVE DIAL 635-4000
|
||
|
||
|
||
|
||
|
||
NOTE: SYMBOL (CR) MEANS CARRIAGE RETURN
|
||
------------------------- SHEET 1 -------------------------- 1 OF 2
|
||
|
||
1. INSURE THE SYSTEM DISK PACKS ARE MOUNTED & READY.
|
||
I.E. ALL SWITCHES IN THE UP POSITION.
|
||
ALL READY LIGHTS ON [OR HEADS ARE LAUNCHED]
|
||
2. SCAN CORE:
|
||
UNLOCK CONSOLE AND DATA SWITCHES
|
||
PUSH THE SWITCHES IN THE FOLLOWING ORDER:
|
||
RESET
|
||
EXAMINE THIS
|
||
STOP PAR
|
||
STOP NXM
|
||
REPEAT
|
||
EXAMINE NEXT
|
||
|
||
3. IF THE LIGHTS ON THE ADDRESS SWITCHES STOP WITH 18 & 19 ON
|
||
YOU WIN. I.E. 600000 IN ADDRESS SWITCHES.
|
||
IF OK CONT TO STEP 4.-----IF NOT OK GO TO SHEET 2
|
||
|
||
4. CLEAR THE FOLLOWING SWITCHES:
|
||
STOP PAR
|
||
STOP NXM
|
||
|
||
5. PUSH THE RESET SWITCH SEVERAL TIMES.
|
||
|
||
--------PREFERRED PROCEDURE--------
|
||
6A. INSURE THAT "READ-IN DEVICE" SWITCHES 4 6 7 8 ARE ON---ONLY
|
||
[LOCATED AT UPPER LEFT OF CONSOLE]
|
||
PUSH THE READ IN SWITCH
|
||
IF WORKING PROPERLY,YOU SHOULD GET"BOOTS"ON CONSOLE...GO TO STEP 7
|
||
IF NOT BACK TO STEP 5.
|
||
--------ALTERNATE PROCEDURE--------
|
||
6B. PUT THE 128K.EXE TAPE INTO THE PAPER TAPE READER.
|
||
INSURE THAT BOOTS TAPE IS POSITIONED PAST THE GARBAGE LEADER...
|
||
...THE LAST LETTER OF WHICH IS AN N .
|
||
PRESS THE FEED SWITCH MOMENTARILY ON READER...TO ARM LOGIC.
|
||
--------INSURE THAT "READ-IN DEVICE" SWITCHES 5 & 9 ARE ON ----ONLY
|
||
[LOCATED AT UPPER LEFT OF CONSOLE]
|
||
|
||
PUSH THE READ IN SWITCH
|
||
[THE PTR SHOULD START READING TAPE]
|
||
IF READ IN IS WORKING PROPERLY YOU SHOULD GET A (CR)
|
||
IN APPROXMATLY 15 SECONDS. IF THERE IS NO (CR) THEN
|
||
GO TO STEP 5...IF OK THEN CONTINUE WITH PROCEDURE...AT STEP 6B.
|
||
--------IF YOU FIND YOURSELF LOOPING BACK TO STEP 5...AND YOU FEEL YOU
|
||
HAVE PROPERLY DONE THE ABOVE THEN GO TO SHEET 7 STEP 1.
|
||
|
||
7. IF YOU WANT TO DUMP CORE TO DISK GO TO STEP 8.
|
||
|
||
I.E. AFTER A MONITOR CRASH.
|
||
IF NO DUMP WANTED GO TO STEP 10.
|
||
|
||
8. INPUT ON THE CTY DSKA:/D(CR)
|
||
|
||
9. WAIT FOR APPROXIMATLY 30 SECONDS...YOU SHOULD GET A (CR)
|
||
FROM BOOTS WHEN IT IS DONE DUMPING. THEN TO STEP 10
|
||
|
||
10. INPUT A (CR) ON THE CTY.
|
||
[A (CR) WITH NO ARGUMENTS WILL LOAD SYSTEM.SAV FROM DISK]
|
||
------------------------- SHEET 1 ------------------------- 2 OF 2
|
||
|
||
11. AT THIS POINT INSURE THAT THE POWER FAIL LAMP IS NOT ON-OR THE
|
||
SYSTEM WILL NOT RELOAD FOR YOU. SEE SHEET 8.
|
||
12.ANSWER SYSCHK WITH Y(CR)
|
||
ANSWER WHY RELOAD WITH THE CLOSEST CAUSE FOR THE RELOAD. ANY ADDITIONAL
|
||
COMMENT YOU CAN OR CARE TO MAKE CAN BE INSERTED AT THIS TIME.
|
||
I.E. WHY RELOAD POWER SECOND ONE TODAY(CR)
|
||
OTHER LOST DPA CONTROLLER(CR)
|
||
OPR I FORGOT TO PUT DPB0 ON LINE(CR)
|
||
SA STAND ALONE FOR DSK FORMATTING(CR)
|
||
ONLY A SPACE BETWEEN THE 'SA' OR 'OPR' OR WHATEVER ...AND THE MESSAGE
|
||
IS NECESSARY.IF YOU INPUT THE WRONG ANSWER YOU WILL GET AN AUTO-
|
||
MATIC LIST OF POSSIBLE RESPONSES. ON A CRASH THAT WAS SOFTWARE CAUSED
|
||
YOU WILL NOT BE ASKED 'WHY RELOAD' BECAUSE THE MONITOR WILL KNOW CAUSE.
|
||
|
||
13.ANSWER DATE DD-MMM-YY(CR)
|
||
|
||
14.ANSWER TIME IN 24 HOUR CLOCK 1500(CR) I.E. 3PM =1500
|
||
|
||
15.ANSWER STARTUP OPTION WITH GO(CR)
|
||
USE ANY OTHER OPTION AT YOUR OWN RISK!!!
|
||
|
||
16.AT THIS POINT IF THEIR IS ANY MEMORY OFF LINE OR A DISK PACK NOT
|
||
AVAILABLE YOU WILL BE ASKED IF YOU WANT IT TO BE 1)ON LINE OR
|
||
2) OFF LINE OR 3) DOWN. IF YOU WANT SAID UNIT TO BE UNAVAILABLE, ALWAYS
|
||
ANSWER WITH 2(CR).
|
||
IF YOU WANT THE DISK UNIT TO BE ON LINE...GO MAKE IT SO AND
|
||
ANSWER WITH 1(CR)
|
||
|
||
17.--------RELOCK THE CONSOLE AND DATA SWITCHES-----------
|
||
THE SYSTEM WILL AUTOMATICALLY RUN THE SPOOLERS ETC AND BE UP
|
||
IN ABOUT 2 MINUTES. IT WILL SEND A 'SYSTEM IS UP' MESSAGE TO ALL
|
||
TTY'S. IF A MESSAGE THAT THE PDP 11 IS NOT RUNNING COMES UP ON
|
||
CTY THEN GO TO STEP 18.
|
||
------- PLEASE MAKE A NOTE IN THE LOGBOOK AS TO WHAT HAPPENED!!!
|
||
|
||
18.TO RELOAD THE PDP11 DO THE FOLLOWING:
|
||
AT PDP11 CONSOLE INSURE THAT ALL FOUR LGHTS ARE ON:
|
||
RUN BUS
|
||
PROC CONSOLE
|
||
IF THEY ARE ON GO TO STEP 18A.
|
||
IF THEY ARE NOT ON PUT HALT SWITCH DOWN
|
||
PRESS START SWI SEVERAL TIMES
|
||
PUT HALT SWITCH UP
|
||
GO TO 18A.
|
||
18A. :W X(CR)
|
||
X-R BOOT11(CR)
|
||
X-/C(CR)
|
||
X-SYS:DC76(CR)
|
||
AT THIS POINT SUBJOB X SHOULD SAY THE PDP11 IS LOADED...OR...
|
||
THE SYSTEM WILL CRASH WITH A 6MS STOPCODE.
|
||
IF IT CRASHES THEN:
|
||
UNLOCK CONSLOE AND DATA SWITCHES
|
||
GO TO STEP 5.
|
||
------------------------ SHEET 2 -------------------------
|
||
|
||
HERE BECAUSE REPEAT EXAMINE DIDN'T GET 192K ON LINE.
|
||
|
||
1.PRESS RESET SWITCH SEVERAL TIMES.
|
||
2.GO TO ALL THREE MEMORIES AND INSURE AWRQ LIGHT IS 'ON'.
|
||
[LOCATED AT BOTTOM LEFT OF INDICATOR PANEL]
|
||
IF NOT.....OPEN FRONT DOOR AND AT BOTTOM RIGHT ON SWITCH PANEL
|
||
THERE IS A RESET SWITCH-PRESS IT & SEE IF AWRQ COMES ON
|
||
IF OK GO TO STEP 3. IF NOT MEMORY IS DOWN [MAKE SURE THE
|
||
LAMP IN THAT POSITION WORKS...USE LAMP TEST INSIDE INDICATOR
|
||
COVER]
|
||
3.INSURE ALL PORTS ARE SELECTED...EACH PORT HAS A SWITCH LABELED:
|
||
SEL DES....ALL SHOULD BE IN SEL POSITION.
|
||
4.TRY A REPEAT DEPOSIT THROUGH CORE:
|
||
SET ALL DATA SWITCHES TO A ONE.
|
||
CLEAR ALL ADDRESS SWITCHES [SINGLY OR USE CLR PB]
|
||
PRESS RESET SWITCH
|
||
PRESS DEPOSIT THIS.. [GOING TO ADDRESS 000000]
|
||
STOP PAR AND STOP NXM SHOULD BE ON AT THIS TIME
|
||
PRESS REPEAT SWITCH
|
||
PRESS DEPOSIT NEXT
|
||
YOU SHOULD GET A MEMORY STOP WITH ADDRESS SWITCHES = 600000
|
||
IF NOT GO TO STEP 5. IF OK CONT.
|
||
|
||
PRESS RESET SWITCH
|
||
CLEAR ADDRESS SWITCHES
|
||
PRESS EXAMINE THIS
|
||
PRESS REPEAT SWITCH
|
||
PRESS EXAMINE NEXT
|
||
YOU SHOULD STOP WITH ADDRESS SWITCHWS = 600000
|
||
IF OK THEN DO DEPOSIT AND EXAMINE CYCLES USING [ABOVE AT STEP 4] ALL ZERO'S
|
||
AND GO BACK FROM WHENCE YOU CAME...SHEET 1 STEP 4.
|
||
|
||
5.IF NOT OK CHECK FOR PARITY ERROR OR NXM. TO DO THIS YOU WILL HAVE TO
|
||
FIND THOSE INDICATORS IN BAY 3.
|
||
|
||
5A. THE PARITY ERROR INDICATOR IS LOCATED AT THE TOP OF BAY 3.
|
||
ROW 3 20TH INDICATOR FROM LEFT.
|
||
IF IT IS ON GO TO SHEET 3.
|
||
|
||
5B. THE NXM (NON EXISTENT MEMORY) INDICATOR IS ALSO IN BAY 3.
|
||
ROW 5 10TH INDICATOR FROM LEFT.
|
||
IF IT IS ON GO TO SHEET 4.
|
||
------------------------- SHEET 3 ------------------------ 1 OF 2
|
||
PARITY ERROR ROUTINE
|
||
|
||
IN THIS ROUTINE WE ARE LOOKING FOR PARITY ERRORS IN CORE--SO THAT WE MAY
|
||
ISOLATE THE BAD MEMORY,DESELECT IT AND RELOAD THE SYSTEM.
|
||
|
||
1.CLEAR ALL SWITCHES AND PRESS RESET SEVERAL TIMES.
|
||
INSURE ADDRESS SWITCHES ARE EQUAL TO 000000.
|
||
|
||
2.SET STOP NXM SWITCH
|
||
SET STOP PAR SWITCH..THESE SWITCHES SHOULD REMAIN ON FOR REST OF PROCEDURE.
|
||
2A. PRESS EXAMINE THIS
|
||
PRESS REPEAT
|
||
PRESS EXAMINE NEXT
|
||
IF ADDRESS SWITCHES STOP AT OTHER THAN 600000 YOU HAVE A PARITY ERROR
|
||
GO TO STEP 3.
|
||
|
||
2B.IF THEY DID NOT STOP THEN:
|
||
PRESS RESET
|
||
CLEAR ADDRESS SWITCHES [=000000]
|
||
SET DATA SWITCHES TO ALL ONE'S
|
||
PRESS DEPOSIT THIS
|
||
PRESS REPEAT
|
||
PRESS DEPOSIT NEXT
|
||
ADDRESS SWI SHOULD STOP EQUAL TO 6000000...IF THEY DO'T CALL DEC F.S.
|
||
PRESS RESET
|
||
CLEAR ADDRESS SWITCHES [=000000]
|
||
PRESS EXAMINE THIS
|
||
PRESS REPEAT
|
||
PRESS EXAMINE NEXT
|
||
IF ADDRESS SWITCHES STOP AT OTHER THAN 600000 YOU HAVE A PARITY ERROR
|
||
GO TO STEP 3.
|
||
|
||
IF THEY DID NOT STOP THEN ONE MORE POSSIBILITY EXISTS:
|
||
PRESS RESET
|
||
CLEAR ADDRESS SWITCHES [=000000]
|
||
SET DATA SWITCHES TO EQUAL 100000 000000
|
||
PRESS DEPOSIT THIS
|
||
PRESS REPEAT
|
||
PRESS DEPOSIT NEXT
|
||
AGAIN ADDRESS SWI SHOULD STOP = 600000...IF NOT CALL DEC F.S.
|
||
PRESS RESET
|
||
CLEAR ADDRESS SWITCHES [=000000]
|
||
PRESS EXAMINE THIS
|
||
PRESS REPEAT
|
||
PRESS EXAMINE NEXT
|
||
IF ADDRESS SWI STOP AT OTHER THAN 600000 YOU HAVE A PARITY ERROR...
|
||
GO TO STEP 3.
|
||
|
||
IF ADDRESS SWI STOP AT 600000 THERE ARE SEVERAL POSSIBILITIES:
|
||
A.YOU HAVE A SPURIOUS PARITY ERROR SOMEWHERE IN CORE. YOU CAN ATTEMPT
|
||
TO ISOLATE IT USING THE ABOVE ROUTINE OR CALL DEC F.S..
|
||
IF YOU ATTEMPT TO ISOLATE IT..READ THE FIRST PART OF STEP 3 NOW,THEN
|
||
GO BACK TO THE BEGINNING OF THIS ROUTINE.
|
||
B.YOU MAY BE TROUBLESHOOTING A NON EXISTENT MEMORY (NXM) ERROR
|
||
RATHER THAN PARITY ERROR.
|
||
C.YOU MAY HAVE MADE A ERROR IN FOLLOWING THIS PROCEDURE.
|
||
------------------------- SHEET 3 ------------------------ 2 OF 2
|
||
HERE BECAUSE WE FOUND A PARITY ERROR IN CORE.
|
||
|
||
3. THE FIRST THING TO DO IS DE-INTERLEAVE THE MEMORIES...IF THEY
|
||
ARE INTERLEAVED. TO CHECK THIS LOOK AT ADDENDUM A AND INSURE
|
||
ALL THE MEMORIES HAVE THE INDICATED SWITCHES IN THE DOWN POSITION.
|
||
|
||
NOW THAT THE MEMORIES ARE NOT INTERLEAVED WE MUST FIND THE PARITY
|
||
ERROR AGAIN...THEREFORE DO PARITY ERROR ROUTINE AGAIN [SHEET 3
|
||
STEPS 2 & 2A ] AND RETURN BELOW TO STEP 3A.
|
||
|
||
3A.THE ADDRESS SWITCHES SHOULD = SOME VALUE < 600000.
|
||
BITS 18 & 19 WILL NOW DIRECT US TO THE BAD MEMORY. THE POSSIBLE
|
||
COMBINATIONS ARE: 18 19 20
|
||
0 0 X
|
||
0 1 X
|
||
1 0 X
|
||
EACH MEMORY UNIT(A,B,OR C) WILL BE EQUAL TO ONLY ONE OF THE ABOVE.
|
||
TAKING THE ADDRESS SWITCHES BITS 18 19 ...MATCH THEM WITH ONE OF
|
||
THE MEMORY UNITS. THIS UNIT MUST BE DESELECTED...SEE ADDENDUM B.
|
||
THE PORT SEL DES SWITCHES (TOTAL OF 4) MUST BE PUT IN DES POSITION.
|
||
THE MEMORY IS NOW OFF LINE.
|
||
|
||
3B.IF THE UNIT YOU DESELECTED WAS 18=1 & 19=0 (UNIT C) YOU NEED TAKE NO FURTHER
|
||
ACTION. RETURN TO PROCEDURE AT SHEET 1 STEP 4.
|
||
IF UNIT TAKEN OFF LINE WAS ONE OF THE OTHER TWO (UNITS A,B) WE MUST RE-
|
||
CONFIGURE THE MEMORIES.
|
||
|
||
3C.WE HAVE TO INSURE THERE IS 128K OF SEQUENTIAL CORE MEMORY ON LINE.
|
||
MAKE THE SWITCHES IN UNIT C EXACTLY EQUAL TO THE SWITCHES OF THE
|
||
DESELECTED UNIT...WITH THE EXCEPTION OF THE PORT SEL DES .
|
||
I.E. UNIT C WILL NOW BE ADDRESED AS THE BAD UNIT WAS AND WILL ALSO
|
||
BE ON LINE.
|
||
ADDENDUM'S C1 & C2 ILLUSTRATE HOW THE TWO REMAINING UNITS SHOULD BE
|
||
ADDRESSED.
|
||
|
||
3D.WE WILL NOW SWEEP CORE TO SEE IF 128K IS ON LINE.
|
||
PRESS RESET SWITCH
|
||
SET STOP PAR
|
||
SET STOP NXM
|
||
PRESS EXAMINE THIS
|
||
PRESS REPEAT
|
||
PRESS EXAMINE NEXT
|
||
IF ADDRESS SWITCHES STOP WITH 400000 (BIT 18 = 1) & NXM FLAG IS UP WE WIN!
|
||
GO TO PROCEDURE AT SHEET 1 STEP 4.
|
||
|
||
IF ADDRESS SWITCHES STOP < 400000 WE LOST...CHECK TO SEE IF STEP 3C WAS DONE
|
||
PROPERLY.
|
||
------------------------- SHEET 4 -------------------------
|
||
|
||
HERE BECAUSE WE FOUND NXM PRIOR TO 192K [ADD SWI NOT EQUAL TO 600000]
|
||
FIRST YOU MUST DE-INTERLEAVE THE MEMORIES...IF THEY ARE INTERLEAVED.
|
||
TO DO THIS INSURE ALL MEMORY UNITS HAVE THE SWITCHES INDICATED
|
||
IN ADDENDUM A IN THE DOWN POSITION.
|
||
|
||
1.PUSH RESET SWITCH.
|
||
CLEAR STOP PAR SWITCH
|
||
CLEAR ADDRESS SWITCHES
|
||
SET STOP NXM SWITCH
|
||
PRESS EXAMINE THIS....LOCATION 000000
|
||
PRESS REPEAT
|
||
PRESS EXAMINE NEXT
|
||
|
||
ADDRESS SWITCHES SHOULD STOP WITH STEPS 2-4 INDICATED. IF YOU GO TO STEP 5..
|
||
....YOU WIN. IF YOU FIND THAT YOU ARE IN A LOOP (STEPS 2-4) THEN GO TO STEP 6.
|
||
|
||
2.IF ADDRESS IS = 000020 THEN UNIT ADDRESSED 18=0 & 19=0 IS THE PROBLEM.
|
||
CHECK ADDENDUM C1 FOR PROPER SWI SETTINGS ON UNIT 18=0 19=0.
|
||
PRESS RESET SWI AND GO TO STEP 1 AGAIN.
|
||
|
||
3.IF ADDRESS IS = 020000 THEN UNIT ADDRESSED 18=0 & 19=1 IS THE PROBLEM.
|
||
CHECK ADDENDUM C2 FOR PROPER SWI SETTINGS ON UNIT 18=0 19=1.
|
||
PRESS RESET SWI AND GO TO STEP 1 AGAIN.
|
||
|
||
4.IF ADDRESS IS = 400000 THEN UNIT ADDRESSED 18=1 & 19=0 IS THE PROBLEM
|
||
CHECK ADDENDUM C3 FOR PROPER SWI SETTINGS ON UNIT 18=1 19=0.
|
||
PRESS RESET SWI AND GO TO STEP 1 AGAIN.
|
||
|
||
5.IF ADDRESS IS = 600000 THEN THERE IS NO PROBLEM...AS THIS IS 192K ON LINE.
|
||
GO BACK TO SHEET 1 STEP 4.
|
||
|
||
6.UNIT YOU ARE LOOPING ON IS BAD. DESELECT BAD UNIT BY PUTTING ALL FOUR
|
||
PORT SEL DES SWITCHES TO THE DES POSITION...SEE ADDENDUM B FOR THEIR LOC.
|
||
|
||
6A.NOW GO TO SHEET 3(2 OF 2) STEP 3B. THERE YOU WILL RECONFIGURE THE
|
||
MEMORIES...AS REQUIRED...EVENTUALLY GETTING BACK TO SHEET 1 STEP 4.
|
||
------------------------- SHEET 5 -------------------------
|
||
HERE BECAUSE OF A HARDWARE/SOFTWARE CRASH
|
||
|
||
1.IF YOU WANT TO DUMP THE CRASHED SYSTEM TO DSK THEN:
|
||
ON CTY INPUT DSKA:/D(CR)
|
||
|
||
IF YOU GET A (CR) ON CTY AFTER ABOUT 60 SECONDS GO TO SHEET 1 STEP 11.
|
||
IF YOU GET NO RESPONSE ON CTY IN 60 THEN DO THE FOLLOWING:
|
||
UNLOCK CONSOLE AND DATA SWITCHES
|
||
SET SWITCH MI PROG DIS[LOCATED AT UPPER LEFT OF CONSOLE]
|
||
SET 30(8) IN ADDRESS SWITCHES..I.E. SET ADDRESS SWI 30 &31 ONLY
|
||
PUT 000000 000007 INTO DATA SWITCHES I.E. SWI 33 34 35 SET
|
||
PRESS DEPOSIT THIS SEVERAL TIMES
|
||
|
||
YOU SHOULD GET MESSAGE ON CTY BOOTS
|
||
IF YOU DO THEN INPUT DSKA:/D(CR)
|
||
AND GO TO SHEET 1 STEP 11.
|
||
|
||
IF YOU DO NOT GET 'BOOTS' MESSAGE ON CTY THEN:
|
||
PRESS STOP SWITCH
|
||
PRESS RESET SWITCH
|
||
GO TO SHEET 1 STEP 5
|
||
------------------------- SHEET 6 -------------------------
|
||
HERE BECAUSE SYSTEM IS POWERED OFF...DUE TO A POWER FAILURE,
|
||
AN OVERTEMP IN COMPUTER ROOM, A DOORS OPEN INDICATION ON KI10,
|
||
OR A CKT BRKR TRIPPED INDICATION ON THE KI10.
|
||
|
||
NOTE: AT THIS POINT A NUMBER OF THINGS CAN HAPPEN. IF THE SYSTEM AUTO-
|
||
MATICALLY RECOVERS FROM THE FAULT [SAY A POWER GLITCH ] THE MONITOR
|
||
WILL DO A POWER FAIL RESTART ... IT MAY SUCCEED/NOT SUCCEED.
|
||
IF IT DOES, THE MAJORITY OF THE USERS SHOULD BE OK...BUT SOME
|
||
JOBS MAY DIE WITH STRANGE INDICATIONS [PARITY ERRORS,BAD IO,ETC].
|
||
|
||
ALSO THE PDP11 MAY STOP & NEED TO BE RESTARTED...IF SO GO TO STEP 4.
|
||
|
||
------- IF THE SYSTEM POWERS UP AND DOWN TWICE IN QUICK SUCCESSION IT IS
|
||
ADVISABLE THAT YOU DO THE FOLLOWING:
|
||
A.UNLOCK THE CONSOLE SWITCHES [BOTH CONSOLE & DATA ]
|
||
B.CLEAR THE ADDRESS SWITCHES...THEN SET ADDRESS SWITCHES 31 & 32.
|
||
C.SET SOME VALUE INTO THE DATA SWITCHES...E.G. SW 31,32 =1
|
||
D.PRESS DEPOSIT THIS
|
||
THE ABOVE IS TO BRING A ORDERLY HALT TO THE MONITOR.
|
||
IN ANY CASE AFTER THE DEPOSIT WAIT 30 SECONDS AND DO STEP E.
|
||
E.PUSH THE POWER SWITCH ONCE...SO IT IS EVEN WITH THE OTHERS.
|
||
THIS IS TO KEEP THE SYSTEM FROM CONTINUOUSLY POWERING UP/DOWN,DUE TO
|
||
------- APPARENT BAD INPUT POWER FROM THE SUBSTATION.
|
||
|
||
|
||
|
||
|
||
IN ANY CASE THE DECISION IS YOURS AS TO CRASH/RELOAD THE SYSTEM
|
||
OR LEAVE IT RUNNING.
|
||
|
||
|
||
|
||
IF OVERTEMP INDICATOR IS ON ...GO TO STEP 1.
|
||
IF DOORS OPEN INDICATOR IS ON...GO TO STEP 2.
|
||
IF CKT BRKR TRIPPED INDICATOR IS ON...GO TO STEP 3.
|
||
|
||
1.THE ONLY LIGHT THAT SHOULD BE 'ON' IN BAY 3 IS THE POWER
|
||
LIGHT...UNLESS IT IS BURNED OUT. IN ANY CASE PUSH THE POWER SWITCH
|
||
ONCE...SO IT IS EVEN WITH THE LAMP TEST SWITCH.
|
||
THE SYSTEM IS NOW INHIBITED FROM POWERING UP...UNTILL SUCH TIME AS YOU
|
||
PUSH THE SWITCH AGAN...AFTER THE CAUSE OF THE OVERTEMP IS DETERMINED.
|
||
|
||
|
||
2.THE 'DOORS OPEN' CKT HAS AN AUXILIARY OVERTEMP CIRCUIT WIRED INTO IT,
|
||
THEREFORE GO TO STEP 1 .
|
||
|
||
3.THIS INDICATOR BEING ON IS BAD NEWS. TAKE NO CORRECTIVE ACTION
|
||
OTHER THAN CALLING DEC FIELD SERVICE...635-8070
|
||
|
||
4.THERE ARE TWO WAYS TO BRING THE PDP11 BACK. DUE TO THE VARIOUS WAYS
|
||
THAT IT CAN CRASH, ONE OR BOTH MAY BE NEEDED TO SUCCESSFULLY RELOAD IT
|
||
. A.PRESS HALT SWITCH DOWN AND PRESS START SWITCH TWICE.
|
||
----THIS WILL CLEAR PDP11 CPU----
|
||
PUT 000602 INTO THE ADDRESS SWITCHES.
|
||
PRESS LOAD ADDRESS-OBSERVE 602 IN LIGHTS.
|
||
TAKE HALT SWITCH OFF----UP, OR EVEN WITH OTHERS----.
|
||
PRESS START SWITCH ONCE.
|
||
|
||
B.ON THE CTY [LA30] INPUT
|
||
:A BOOT11
|
||
THIS WILL AUTOMATICALLY REBOOT THE 11 VIA OPSER
|
||
------------------------- SHEET 7 ------------------------- 1 OF 1
|
||
|
||
HERE BECAUSE BOOTS TAPE WOULD NOT READ IN PROPERLY.
|
||
|
||
1.ONE POSSIBLE PROBLEM IS THAT THE BOOTS TAPE YOU ARE USING IS BAD. FIND
|
||
ANOTHER 96K [0R 128K] AND GO BACK TO SHEET 1 STEP 5.
|
||
IF THEY DO NOT WORK EITHER THEN GO TO NEXT STEP.
|
||
|
||
2.SET READ-IN DEVICE SWITCHES 4 5 & 6 ONLY----TAKE 9 OFF.
|
||
GET A MAGTAPE LABELED MAGRIM AND MOUNT IT ON DRIVE 0.
|
||
--------WE ARE NOW GOING TO TRY AND GET THE MONITOR OFF THE MAGRIM TAPE.
|
||
|
||
3.MTA0 SHOULD BE ENABLED AND READY TO GO.
|
||
PRESS RESET SWITCH
|
||
PRESS READ IN SWITCH
|
||
|
||
YOU SHOULD SEE THE MAG TAPE MOVE TAPE...IF IT DOES GO TO SHEET 1 STEP 12.
|
||
|
||
IF IT DOES NOT MOVE THEN:
|
||
PRESS THE STOP & RESET SWITCHES.......AND CALL DEC FIELD SERVICE
|
||
------------------------- SHEET 8 -------------------------
|
||
|
||
HERE TO FIND POWER FAIL LAMP AND HOW TO TURN IT OFF
|
||
|
||
1. BAY 3[OPERATOR'S CONSOLE] TOP HALF..THE BOTTOM ROW OF LAMPS
|
||
THE XXX LAMP FROM THE LEFT IS THE POWER FAIL.
|
||
|
||
2. IF IT IS NOT ON-AND LAMP TEST LIGHT'S IT AS OK- GO TO STEP X.
|
||
IF IT IS ON DO THE FOLLOWING:
|
||
UNLOCK CONSOLE AND DATA SWITCHES (IF NOT ALREADY)
|
||
INTO THE DATA SWITCHES DEPOSIT 700600 400000.
|
||
--THIS EQUALS SWITCHES 0 1 2 9 10 AND 18 ON--
|
||
PRESS RESET SWITCH
|
||
PRESS XCT SWITCH (NEXT TO RESET SWITCH)
|
||
THE POWER FAIL LAMP SHOULD GO OUT.
|
||
IF IT DOES NOT,RECHECK THE DATA SWITCHES AND TRY AGAIN,IF
|
||
IT STILL DOES NOT GO OUT CALL DEC FIELD SERVICE.
|
||
|
||
IF THE LAMP GOES OUT IT IS ADVISABLE TO CLEAR CORE AT THIS TIME
|
||
AS THERE MAY BE PARITY ERRORS AS A RESULT OF THE POWER FAILURE.
|
||
|
||
TO CLEAR CORE DO A DEPOSIT NEXT FUNCTION:
|
||
PRESS RESET SWITCH
|
||
CLEAR BOTH ADDRESS AND DATA SWITCHES
|
||
PRESS DEPOSIT THIS
|
||
PRESS PAR STOP, NXM STOP, AND REPEAT SWITCHES
|
||
PRESS DEPOSIT NEXT SWITCH
|
||
|
||
THE ADDRESS SWITCHES WILL STOP WITH 18 AND 19 ON A ONE |